Go contents Go Navigation Go sitemap

ECOSENSE BEST PARTNER FOR YOUR GREEN LIFE

Compact Current Transformer

home  Business > Compact Current Transformer

sEMS (FEMS, BEMS) Eco CT®Open/Closed split converter

sEMS (FEMS, BEMS) Eco CT ®
Open/Closed split converter

Precise measuring without having to cut off power lines

Low phase difference

Product available in large/medium/small size

Easy open/close (manual opening is available)

High output voltage

Superior accuracy

sEMS (FEMS, BEMS) Eco CT
Model ES-CT16L ES-CT24L ES-CT36L
Current transformation ratio 120 A : 40 mA 200 A : 100 mA 500 A : 250 mA
Applying current In = 120 A (50 Hz / 60 Hz) In = 200 A (50 Hz / 60 Hz) In = 500 A (50 Hz / 60 Hz)
Maximum current 200 A 500 A 1,025 A
Clamping scope 16 mm 24 mm 36 mm
Winding ratio 3000 : 1 2000 : 1 2000 : 1
Winding resistance 250 ± 15 Ω 59 ± 6 Ω 39 ± 3 Ω
Nominal Phase Angle Error 55 ± 20 min 25 ± 20 min 15 ± 5 min
Nominal Ratio Error 0.5 % 0.5 % 0.3 %
Nominal Linearity Within ± 0.5 % Within ± 0.5 % Within ± 0.5 %
Standard Accuracy 1.0 Class 1.0 Class 1.0 Class
Operating frequency 20 Hz to 400 Hz 20 Hz to 400 Hz 20 Hz to 400 Hz
Output protection 7.5 Vp 3.0 Vp 3.0 Vp
Weight 70 g 300 g 300 g
Insulation Resistance DC 500 V / 100 MΩ more DC 500 V / 100 MΩ more DC 500 V / 100 MΩ more
Dielectric strength AC 1500 V / 1 min AC 2000 V / 1 min AC 2000 V / 1 min
Allowed number of release Around 100 times Around 100 times Around 100 times
Service temperature & humidity - 20 ℃ ~ + 50 ℃, ≤ 85 % RH - 20 ℃ ~ + 50 ℃, ≤ 85 % RH - 20 ℃ ~ + 50 ℃, ≤ 85 % RH
Preservation temperature & humidity - 30 ℃ ~ + 90 ℃, ≤ 85 % RH - 30 ℃ ~ + 90 ℃, ≤ 85 % RH - 30 ℃ ~ + 90 ℃, ≤ 85 % RH